  4. Single-phase grid voltage attributes tracking for the control of grid power converters
 
  • Details

Single-phase grid voltage attributes tracking for the control of grid power converters

Source
IEEE Journal of Emerging and Selected Topics in Power Electronics
ISSN
21686777
Date Issued
2014-12-01
Author(s)
Subramanian, Chandrasekaran
Kanagaraj, Ragavan  
DOI
10.1109/JESTPE.2014.2341045
Volume
2
Issue
4
Abstract
Grid interfacing power converters are indispensable for renewable energy conversion schemes. Fast and precise detection of grid signal parameters is essential for effective operation and control of these converters. For such applications, synchronous reference frame phase-locked loop (SRF PLL) involving two orthogonal signals (OS) is widely deployed. For the single-phase system, this requires another signal orthogonal to the input. In this paper, single-phase SRF PLL with fixed sampling period sliding discrete Fourier transform (SDFT) filter as OS generator is proposed. Additionally, this filter is capable of rejecting dc offset and harmonics present in the grid voltage. With this arrangement, the loop filter of PLL need not be equipped with filtering capability. Therefore, PLL could be designed with larger bandwidth, which will result in better transient performance. However, SDFT output will be erroneous with asynchronous sampling, under grid frequency drift. With suitable study, relation between those errors and deviation of frequency from nominal value is established. Using this relation, error compensation at any grid frequency can be achieved. To validate the proposed method, various grid abnormalities are emulated with the aid of programmable power source and dSPACE real-time controller board. The effectiveness of the proposed scheme is demonstrated through experimental investigations.
Unpaywall
URI
https://d8.irins.org/handle/IITG2025/21219
Subjects
DC offset | grid synchronization | phase-locked loop (PLL) | sliding discrete Fourier transform (SDFT) | synchronous reference frame PLL (SRF PLL)